AMR system based on technical means complex Micron AMR system based on technical means complex Micron
AUTOMATED INFORMATION-MEASURING SYSTEM FOR COMMERCIAL ENERGY ACCOUNTING (AIISKUE) The factory developed its own certified measuring and computing complex “MICRON”, which allows maintaining multi-tariff energy consumption accounting on the basis of electricity supply meters with the communication interface by specification ÅIA RS-485. Technical means of “MICRON” complex belong to the products of the State system of industrial automation equipment (GSP) and ensure: - measurement and storage of information on electric energy consumption by means of electricity supply meters at metering points;
- gathering of information stored in the electricity supply meters through switched channels, consolidation and processing of this information in the metering stations;
- long-term storage, processing and display of information on energy consumption in the metering stations.
BASIC FUNCTIONS OF AMR SYSTEM BASED ON TECHNICAL MEANS COMPLEX “MICRON”
- Electrical quantities measured values reading of electricity supply meters.
- Programming of time zone limits for multi-tariff accounting, programming of date of switch to daylight-saving time/date of revert to standard time.
- Automatic current date and current time correction for every electricity supply meter by the inner clock of the main server system (maximal time discrepancy is ±10 seconds per day).
- Keeping of the AMR system operation start date and time.
- Automated remote data collection directly to the data collection and processing units using radio and GSM channels on the operator request once every 10 days, monthly, quarterly, yearly (depending on the requirements specification of the Customer the periods can be changed).
- Determination and registration of non-metered energy consumption occurrences in the AMR system based on standard analytical procedures.
- Modular construction of the AMR system.
- Possibility to extend the AMR system system without additional expenditures when connecting new components.
ORGANIZATION VARIANTS OF AMR SYSTEM BASED ON TECHNICAL MEANS COMPLEX “MICRON”
Version of AMR system arrangement on the basis of KTS MICRON: application of power lines (PLC-technology) for data forwarding to USD(data acquisition unit) with further transmission by GSM-networks in GPRS or CSD mode. >>>

Schematic of TMC MICRO-based AMR-system with application of PLC-technology.
USED INSTRUMENTS
Eectric power meters |
SEB-2À or SEB-4ÒÌ-compatible data transfer protocols |
SEB-1TM.02D with PLC-modem.
Multifunctional meter with multi-tariff calculation of electricity in single-phase networks.
Meter has integral PLC-modem for work in AMR system and optical port for local data reading and parametrizing. |
Nominal voltage - 230 V
Nominal (maximum) current - 5 (75) À
Accuracy class - 1,0
Number of tariffs - 4
Communication interface – optoport or PLC.
Load control function.
SEB-1ÒÌ.02D modification is to be fixed on DIN-bar. |
PLC-modem Ì-2.01
The device is designed for data transmission over power line 220 V. |
Supply voltage from 85 to 265 V
Power consumption maximum 10 VA, 4 W
Data transfer rate in channel of PLC – 2400 bit/s;
Interfaces:
single phase low voltage network 230 V with power-line frequency;
RS-485, rate - to 38400 bit/s
Quantity of electric power meters, connected via RS-485 - to 32
Communication range peer-to-peer - to 2 km |
Data acquisition unit USD-2.01
The unit on basis of the industrial controller ICP CON I-7188XA under direction special software is designed for work of system of data acceptance by power mains and RS-485. Data communications for information centre are realized by RS-485 locally or with GSM-communicator C-1.01 remotely. |
Supply voltage - 220 V, 50 Hz
Power consumption - maximum 25 W
PLC network: data transfer rate - 2400 bit/s.
External interfaces: RS-485, PLC
Quantity of maintained account points - to 430
Types of maintained protocols of electric power meters:
SEB-2À-compatible;
SEB-4ÒÌ- compatible
Modes of access to electric power meters :
Point-to-point channel;
virtual channel (automatic polling) |
Data acquisition unit USD-2.02
The unit on the basis GSM-terminal Siemens TC 65 under direction special software is assigned for work of system of data acceptance by power mains. Data communications for information centre are realized by GSM-channel remotely. |
Supply voltage - 220 V, 50 Hz
Power consumption - maximum 25 W
PLC network: data transfer rate - 2400 bit/s.
External interfaces: RS-485, PLC
Quantity of maintained account points - to 430
Types of maintained protocols of electric power meters:
SEB-2À-compatible;
SEB-4ÒÌ- compatible
Modes of access to electric power meters :
Point-to-point channel;
virtual channel (automatic polling) |
GSM-Communicator C-1.01
Communicator is designed for coupling of networks of mobile wireless telephony network of GSM-900/1800 standard with an object local network of RS-485. |
Supply voltage - 220 V, 50 Hz
Characteristics of GSM/GPRS module:
number of ranges 2 (900/1800 MHz);
transmitter output power:
a) class 4 at frequency 900 MHz 2 W;
b) class 1 at frequency 1800 MHz 1 W
GPRS class 10;
CSD (nontransparent) 9600 bit/s;
supply voltage of SIM-card 3 V or 5 V |
GSM-modem
The device is designed for arrangement of wireless communication over GSM-channels between GSM-communicator and IC (Information center). |
The unit is designed for organization of wireless network by GSM-channels between GSM-communicator and Information centre. Modem is recommended for use from Frunze Plant. Modem work in standard GSM 900/1800 is necessary only in case of organization of network’s channel with server by CSD (in case of absence of external static IP-address). In case of use of CSD-condition the value of network’s services is higher usually than GPRS-condition. Only one DAU is interrogated at once in the presence of one modem on the server in CSD-condition.
|
SYSTEM ADVANTAGES
- Ease in deployment and commissioning.
- High reliability of data transmission.
- Flexible polling configuration.
- Scalability.
- Flexible equipment configuration for set task.
- Low software management complexity.
Variant of AMR system based on technical means complex “MICRON”: installation of the GSM communicator for data collection from electricity supply meters and data transfer using GSM networks in GPRS or CSD mode. >>>

| SINGLE-PHASE MULTIRATE ELECTRIC POWER METERS |
|
|
-
Signal digital processing .
-
Built-in real-time timer.
-
Communication interface RS-485.
-
Nonvolatile memory.
-
Readouts and power profile storage (from 57 to 112 days depending on electric power meter model).
-
Built-in load shedding device.
|
|
|
RADIOADAPTER
The device transmits information from user sensor via radio channel at a distance to 150 meters for processing and further transfer. |
|
Supply – 220 V, 50 Hz
Self-contained supply
accumulator 3.6 V. 650 mAh
Frequency range – 434.720 ± 0.008 MHz
User interface - RS-485
|
|
|
GSM-COMMUNICATOR
The device is designed for accepting of smart sensor readings with the aid of radio modem or via interface RS-485 and further transmission to information center. Double-range GSM-modem (EGSM 900/1800 MHz), two SIM-cards, data cryptographical security. |
|
Supply -220 V, 50 Hz
Frequency range of built-in radio modem – 434.720 ± 0.008 MHz
Information exchange frequency ranges with IC:
GSM 900 ....... 880-960 MHz
GSM 1800 .... 1710-1880 MHz
Operating temperature range - from -30 to +60 oC |
|
|
GSM-MODEM
The device is designed for arrangement of wireless communication via GSM-channels between GSM-communicator and IC. |
|
Modem (at Customer’s option), operating in standard GSM 900/1800. |
|
INFORMATION CENTER PROVIDES THE FOLLOWING:
- Acquisition and validation of electric energy data from all monitoring sites, equipped by KTS MICRON.
- Database creation, information processing, storage, display and documenting for commercial and technical energy accounting.
- Database creation for monitoring of energy imbalance values.
- Generation of data about used energy for mentioned above control devices.
Variant of AMR system based on technical means complex “MICRON”: use of a wire telephone line for remote communication of an electricity supply meters package with the control station. >>>
AMR system software based on technical means complex “MICRON”
| SINGLE-PHASE MULTIRATE ELECTRIC POWER METERS |
|
|
-
Signal digital processing .
-
Built-in real-time timer.
-
Communication interface RS-485.
-
Nonvolatile memory.
-
Readouts and power profile storage (from 57 to 112 days depending on electric power meter model).
-
Built-in load shedding device.
|
|
|
INTERFACE TRANSDUCER (IT)
IT-1 provides signal conversion of interface RS-232; IT-2 – signal conversion of standard USB 1.1 into conductively uncoupled electric signals of interfaces RS-485, and vice a versa. |
|
Length of communication line- to1200 m.
Rate of exchange:
IT-1 ....... 300 to 19200 baud
IT-2 ....... 300 to 38400 baud
Operating temperature range - -40 to +70 oC
|
|
|
TRANSPONDER
It id designed for transmission line extension, provides transmission of interface RS-485 information signals and electrical isolation of these signals from both sides. |
|
Rated voltage (Urated) – 220 V
Operating range – 0.9 to 1,1 Urated
Network frequency - 50±2,5 Hz
Operating temperature range - -20 to +50 oC
|
|
|
MODEM
Auxiliary device for arrangement of communication between arrays of meters and information center (IC) via static communication lines. |
|
Dial-up modem (at Customer’s option), supporting standard command transfer protocol AT. |
|
INFORMATION CENTER PROVIDES THE FOLLOWING:
- Acquisition and validation of electric energy data from all monitoring sites, equipped by KTS MICRON.
- Database creation, information processing, storage, display and documenting for commercial and technical energy accounting.
- Database creation for monitoring of energy imbalance values.
- Generation of data about used energy for mentioned above control devices.
Software AMR system on the basis of KTS MICRON >>>
Software of ÊÒS MICRON is created on the multilevel principle and consists of the following programs:
- System configurator.
- Data acquisition module.
- Task planning module.
- Transport module.
- Database server.
- User module.
- Report writer module.
- MSSql Server Express.
|
|
Communication programs -
Data acquisition module and
Task planning module.
It provides automatic electric power meter polling via switched lines on the basis of preformed task list. |
Setup program - AMR system configurator.
It is designed for description of measuring system general structure, creation of procedural rules for data exchange between operator station and electric power meters.
|
|
|
Supervisor programs - Transport module and Database server.
It provides database control and monitoring of data exchange between programs of ÊÒS MICRON
|
Operator program - User module.
It allows to review collected data, to send signal for load consumption constraint, to create database about energy consumption by users in format, coordinated with retail supplier.
|
 |
 |
System of data review and report writing- Report writer module.
Software operates at IBM-compatible computers (under operating systems Windows 2000, Windows XP or Windows 2003).
|
CHARACTERISTICS AND ADVANTAGES OF AMR SYSTEM BASED ON TECHNICAL MEANS COMPLEX “MICRON”
- Displaying, preparation in electronic format and printing on paper of the processed information output forms; energy consumption database creation in format approved by the energy supply company.
- Computer-aided testing of measuring channel operability.
- Possibility to form and send a signal for limitation of consumable load or consumer disconnect for late payment of electrical energy (to be approved by the Customer).
- Preparation of the feeder and transformer station balance in the preset time.
- Electricity supply meters control out of any place, where access to INTERNET or GSM/GPRS network is available.
- Timely detection of illegal energy consumption by consumers.
|
|
|
New products
Time-schedule of workshops
Copyright Copyright © 2010 Nizhny Novgorod Factory named after M.V. Frunze. All rights reserved.
|