PURPOSE AND FIELD OF APPLICATION

   The meter is designed for accounting of active energy in three-phase, three- or four-wire power circuits of a.c. with the frequency of 50Hz, independently or as a component of any automated systems for commercial energy accounting (ASKUE), including those that carry out energy consumption control in accordance with the quantity of the pre-paid electrical power.

NORMATIVE AND LEGAL BACKING

    IEC 62052-11:2003

TECHNICAL FEATURES

  • Internal tasksetter.
  • The liquid-crystal display indicates the amount of the consumed active energy in kilowatt-hour with the accuracy of one thousandth of a unit.
  • Nonvolatile memory.
  • Electronic seal (option).
  • Two programmable pulse outputs for commercial and technical accounting.
  • RS-485 communication interface.
  • Reading device for smart cards with an electronic circuit.

FUNCTIONAL CAPABILITIES

  • Exchange of information from a personal computer through RS-485 communication interface or by means of an electronic smart card.
  • Registration and storage of the data on the consumed electrical energy as per each tariff zone with the possibility to scan the information on a liquid-crystal display:

  •     with total accrual accounting;
        for each of preceding 11 months;
        with exceeding the power limit.
  • Setting power and electrical energy limit.
  • Registration and storage of the time data when the meter was energized and de-energized and registration of the time when the meter’s terminal cover was opened.
  • Automatic changing-over to ‘summer’ or ‘winter’ time.
  • Assigning a tariff schedule for every day of the week, taking into consideration holidays, current time, day of the week, date, month, year, category of a consumer.
  • Transmitting a signal from the pulse output to the actuator, which switches on/off the consumer’s load when the consumer exceeds the fixed limits.
  • Protection against unauthorized changing of the information, entered and stored in the meter.
  • Effecting payments for the consumed electrical power under the made out factual account or by advance payment with the help of electronic cards.

TECHNICAL DATA

Quantity

Value

Nominal voltage, V

3220/380

Network frequency, Hz

50±2,5

Nominal (maximum) current,

5 (50)

Accuracy class

1,0

Sensitivity in each phase,

0,0125

Total power consumed by every serial circuit of the meter, at nominal current and nominal frequency, V·

not more than 0,5

Power consumed by every voltage circuit at nominal voltage:
    active, W
    total, V·

not more than 0,8
not more than 1,5

Telemetric output transmission ratio, pulses/kwh:
    in the main mode
    in calibration mode

500
16000

Fixed and maximum working temperature range, °

from – 40 to +55

Recalibration interval, years

6

Average error-free running time, h

55000

Average service life till overhaul, years

30

Measurements of the meter, mm

17032577

Mass of the meter, kg

not more than 1,5

 