Models which are not more series-produced PSCH-4ÀR.05.2 PURPOSE AND FIELD OF APPLICATION The meter is intended for accounting of active and reactive electrical energy in three-phase, three- or four-wire power circuits of a.c. with the frequency of 50 Hz. It can be used either independently or as a component of any information-measuring systems. NORMATIVE AND LEGAL BACKING IEC 62052-11:2003 TECHNICAL FEATURES - Two electrical and mechanical reading devices indicate separately the amount of the consumed active and reactive electrical energy.
- Two telemetric outputs: one for each kind of energy.
- Current transformers are used as current sensors.
- LED indication of the current in the load circuit: the more the load, the more often the LED blinks.
- When manufacturing printing boards, SMD assembling technology is used.
TECHNICAL DATA Quantity | Value | Nominal voltage (Unom), V | 3õ57,7/100 3õ220/380 | Network frequency, Hz | 50 ± 2,5 | Frequency range of measuring network, Hz | from 47,5 tî 52,5 | Nominal current (Inom), À | 5 | Maximum current, À | 7,5 | Accuracy class when measuring active (reactive) energy | 0,5 S (1,0) or 1,0 (2,0) | Sensitivity in each phase, À | 0,005 (class 0,5 S (1,0)) 0,0125 (class 1,0 (2,0)) | Total power consumed by every serial meter’s circuit at nominal current and nominal frequency, V·À | not more than 0,3 | Power consumed by every voltage circuit at nominal voltage: active, W
total, V·À | 0,3 (Unom=57,7 V), 0,5 (Unom=220 V) 1,5 (Unom=57,7 V), 7,5 (Unom=220 V) | Telemetric output transmission ratio, pulses/kwh: in the main mode in calibration mode | 5000 (Unom=57,7 V), 1000 (Unom = 220 V) 160000 (Unom=57,7 V), 32000 (Unom= 220 V) | Working temperature range, °Ñ | from – 40 tî +55 | Recalibration interval, years | 8 | Average error-free running time | 70000 | Average service life till overhaul, years | 30 | Measurements, mm | 325õ170õ70 | Mass, kg | not more than 1,5 | |