PSCH-3R.07D

PURPOSE AND SCOPE OF APPLICATION
    Meters are designed for accounting of active and reactive energy in three-wire and four-wire alternating current mains with frequency 50 Hz.
    Electric power meters may be used independently or in the composition of automated information and measuring systems of electric power control and metering (AEPCM).

REGULATORY GROUNDWORK
IEC 62052-11:2003

TECHNICAL FEATURES OF ELECTRIC POWER METER

  • Communication interface RS-485, optical port.
  • Rate of exchange via RS-485- from  1200 to 38400 baud.
  • Rate of exchange via optoport - to 9600 baud.
  • Simultaneous operation via both ports is allowed.
  • Non-volatile memory.
  • Daily self-testing of program memory.
  • Light-emitting diode indication of active and reactive consumption.
  • Two programmed pulsed outputs to 6 modes.

FUNCTIONAL CAPABILITIES OF ELECTRIC POWER METER
Electric power meters provide measurement, recording and holding in nonvolatile memory and also interface reading of the following:

  • values of measured active and reactive energy by accrued total from the date of manufacture according to all tariffs;
  • values of instantaneous load power.

    Electric power meters provide measurement (reference value) and reading via interface of the following parameters:

  • values of measured active and reactive load power in all phases and gross power;
  • values of voltage and current in all phases.

      Electric power meters may provide reading and reprogramming via interface of the following parameters:
consumer category;
power limit;
electric power meter pulsed output operation modes: calibration, telemetering, connection, disconnection, monitoring.;
indication mode and indication period within the range from 6 to 60 seconds.
Electric power meters may be reprogrammed via communication interface: exchange rate via RS-485, common password, individual password, address, password for recording.
In case of threefold entering of invalid password for recording, electric power meter interlocks recording channel for 24 hours of normal job.
Electric power meters provide display of the following: 

  • active and reactive electric power consumption;
  • current active and reactive power in each phase and cumulative value;
  • voltage and current in each phase;
  • monthly electric power consumption.

    Flashing of light-emitting diode indicators "kWh"  or "kvarh testifies measurement of active or reactive energy accordingly.

TECHNICAL SPECIFICATIONS OF ELECTRIC POWER METER

Value description

Value

Rated voltage, V

3(120-230)/(208-400) or 357.7/100

Specified operating voltage range, V

0.9 to 1.1 Urated

Extended operating voltage range, V

0.8 to 1.15 Urated

Extreme operating voltage range, V

0 to 1.15 Urated

Base (Ib)/maximum (Imax.) current for electric power meters of direct connection,
Rated (Irated)/maximum(Imax.) current for electric power meters of transformer connection,

5/7.5 or 10/100
5/60

Frequency rated value, Hz

50

Preoscillation current (sensitivity) during measurement of active/reactive energy, , max., for electric power meters:
Ib (Imax.) - 5(60) , accuracy class 1/2
Ib (Imax.) - 10(100) , accuracy class 1/2
Irated (Imax.) - 5(7.5) , accuracy class 1/2
Irated (Imax.) - 5(7.5) , accuracy class 0.5S/1


0.02/0.025
0.04/0.05
0.01/0.015
0.005/0.01

Power consumption, V (W), max:

    in voltage circuit

2 (1.5)

    in current circuit

0.1

Operating temperature range, o

-40 to +60

Number of tariffs

1

Rate of information exchange via optical port, bit/s:

    via RS-485

1200, 2400, 4800, 9600, 19200, 38400

    via optical port

9600

Time of information preservation on power-off, years

10

Calibration interval, years

10

Electric power meter guarantee period, months

36

Mean time between failures, h

88000

Average electric power meter service life, years

30

Electric power meter weight, kg

1.0

Electric power meter dimensions, mm

17111067

ELECTRIC METER VERSIONS


Electric power meter version designation

Accuracy class of measurement of active/reactive energy

Transfer ratio in basic mode (in calibration mode), pulse/kWh (pulse/kvar∙h)

Communication interface

Urated = 3(120-230)/(208-400) V, Ib ( Imax. )=5(60)
(of direct connection)

PSCH-3R.07D.112

1/2

500 (10000)

RS-485

PSCH-3R.07D122

1/2

500 (10000)

optoport

PSCH-3R.07D.132

1/2

500 (10000)

RS-485, optoport

Urated =3(120-230)/(208-400) V, Ib ( Imax. )=10(100)
(of direct connection)

PSCH-3R.07G112.1

1/2

500 (10000)

RS-485

PSCH-3R.07D.122.1

1/2

500 (10000)

optoport

PSCH-3R.07D132.1

1/2

500 (10000)

RS-485, optoport

Urated =3(120-230)/(208-400) V, Irated ( Imax. )=5(7,5)
(of electric power meters, connected via current transformer)

PSCH-3R.07D.132.2

1/2

5000 (100000)

RS-485, optoport

PSCH-3R07.D32.4

0,5S/1

5000 (100000)

RS-485, optoport

PSCH-3R.07D.112.2

1/2

5000 (100000)

RS-485

PSCH-3R07D.112.4

0,5S/1

5000 (100000)

RS-485

PSCH-3R.07D122.2

1/2

5000 (100000)

optoport

PSCH-3R.07D.122.4

0,5S/1

5000 (100000)

optoport

Urated =357,7/100V, Irated ( Imax. )=5(7,5)
(of electric power meters, connected via current and voltage transformer)

PSCH-3R.07D.132.3

0,5S/1

5000 (100000)

RS-485, optoport

PSCH-3R.07D.112.3

0,5S/1

5000 (100000)

RS-485

 